Maintained or non-maintained emergency lighting

By Christiaan Boersma   •   8 minuten lezen

Dauerschaltung oder Bereitschaftsschaltung bei der Notbeleuchtung

The most important difference is easily explained: with maintained mode, an emergency light is already illuminated during normal operation, whereas with non-maintained mode, it only lights up when the general power supply fails. Which variant is the right one, however, is not a matter of personal preference. The decisive factors are the function of the light, the required visibility during occupancy, and the specific requirements of the building.

To help you better understand the appropriate operating mode, we explain below—building on the article All about emergency lighting —when maintained mode is typical, when non-maintained mode is often sufficient, and what role switching, system design, as well as maintenance and testing play in practice.

When the light actually illuminates: normal operation vs.Power failure

For differentiation, one question is crucial: Is the luminaire already active during everyday operation, or is it only switched on in the event of a fault?

Operating mode During normal operation In the event of a power failure After power is restored
Maintained mode The luminaire is switched on and visible during regular operation. It remains in operation as an emergency luminaire, now powered by the emergency power supply, battery, or central system. Depending on the system, it switches back to the normal power supply automatically.
Non-maintained mode The luminaire remains off during normal operation. It switches on automatically if the general power supply fails and then provides the safety function. When the mains power returns, it switches back to standby mode.
Switched maintained operation Special case: The luminaire is switched together with the general lighting and therefore only illuminates when the general lighting is switched on. In an emergency, it still takes over the safety function and must be available independently of the normal switching. After the fault, the status returns to the normal switching of the general lighting.

In practical terms, this means: Maintained operation ensures permanent visibility, non-maintained operation provides light precisely when emergency lighting during a power outage is needed.

Where maintained operation is common - and where non-maintained operation is sufficient

Which operating mode is used depends heavily on the function of the luminaire.These practical cases help with classification:

  • Emergency exit signs are often planned for continuous operation when the marking must be visible at all times during operating hours. This is especially relevant where escape routes must be permanently and clearly identifiable.
  • Luminaires for escape routes or anti-panic areas often operate in maintained mode when their primary task is to function during a power failure. They must then be available immediately, but do not necessarily need to be illuminated all day.
  • The lighting concept may deviate from this. Escape route lighting can also be operated continuously or switched on a case-by-case basis if the use of the area or visibility requirements demand it.
  • Electrically illuminated signs are not the same as photoluminescent or externally illuminated safety signs. With electrically illuminated signs, visibility is created by the luminaire itself; with other solutions, this is achieved differently. Therefore, the question of maintained or non-maintained operation must be evaluated differently there.
  • For practical purposes in our product range, this means: In the case of LED emergency lighting and escape route lighting, not only the luminaire itself is important, but also its intended operating mode. The fact that two products look similar does not automatically mean they are designed for the same type of circuit.

Safety lighting, emergency lighting, and emergency lighting systems clearly categorized

In everyday use, these terms are often used interchangeably. However, making the distinction is helpful for planning. Emergency lighting generally refers to lighting that becomes operational when the normal power supply for general lighting fails. Safety lighting is the safety-related part of that.It therefore doesn't just serve to ensure that "there is light somewhere," but is intended to provide orientation, the safe evacuation of an area, or the safe continuation of critical activities.

A single emergency light is merely one building block. When referring to an emergency lighting system, it means the entire system that maintains this function in the event of a power failure. Depending on the design, this includes the lights, the switching unit, the power supply technology, and the monitoring system.

Typical power supply principles include solutions withsingle batteries or central batteries : With single-battery emergency lights, the power supply is integrated into each individual light, whereas central battery systems supply multiple lights from a central location. Additionally, there are the appropriate emergency power components that ensure switching and operation in an emergency.For battery-based solutions, integrated batteries or central battery systems take over the power supply as soon as the normal power supply fails.

So, anyone asking what the difference is between emergency lighting and safety lighting can easily remember it this way: Not all emergency lighting describes a specific protective function, whereas safety lighting certainly does.

What requirements the circuit type dictates

Whether maintained or non-maintained operation is correct depends on the use of the building, the function of the luminaire, and the regulations for the specific property. Therefore, the circuit type is not simply chosen freely, but derived from the requirements.

At its core, it comes down to three questions. First: Must the luminaire or sign be visible during normal usage hours? If so, this often points to maintained operation or switched maintained operation.Second: Must it switch automatically in the event of a normal power failure? This automatic availability is central to safety functions. Third: Can the system reliably provide the required operating time in an emergency? This requires not only the correct luminaire, but also the appropriate power supply technology.

Another important factor is switching back to normal operation. In many cases, this happens automatically as soon as the power supply is stable again. However, there are situations where immediate switching back is not advisable, such as during brief voltage fluctuations, in test mode, or when the control system first needs to restore a safe state. The specific design depends on the system.

Standards and regulations naturally play a role here.For practical decisions, however, they can usually be broken down into understandable criteria: visibility at the right time, safe automatic switching, and sufficient availability in an emergency.

What consequences your choice has for energy, technology, and operations

The choice between maintained and non-maintained operation affects not only visibility, but also ongoing operations:

  • Energy use and operating hours: A luminaire in maintained operation is in use significantly longer. This means more operating hours and continuous energy consumption. With non-maintained operation, these operating hours are largely eliminated during normal operation, but the luminaire must start safely and immediately in an emergency.
  • Technical component stress: More operating hours affect electronics, the light source, and potentially thermal stress. In standby circuits, on the other hand, continuous stress is less of a priority than the reliability of activation after a longer waiting period.
  • Start behavior in an emergency: Especially in standby circuits, it is important that light is available in a very short time. Therefore, the driver technology, switching logic, and luminaire design must match the application. Delays, unstable start behavior, or unsuitable components are more critical here than in a luminaire that is already illuminated.
  • System design and compatibility: Whether self-contained emergency luminaire, central battery system, or other power supply solution: the operating mode must match the entire system.Relevant factors include switching states, charging functions, reporting behavior, and how the system responds to power failures and power restoration.
  • LED technology improves a lot, but it does not replace proper planning: Modern LED emergency lighting reduces several classic drawbacks of older systems, such as through more efficient lighting technology and often more compact designs. However, this does not change the basic requirements. Visibility during operation, reaction time in emergencies, and appropriate power supply technology remain crucial.
  • Operational monitoring: For larger or more technically demanding installations, monitoring the luminaires and the system can be an important factor. Self-test functions or centrally monitored systems can facilitate ongoing operations, but they do not change the fundamental question of whether the luminaire must be visible during daily operations or only activate in an emergency.

Why maintenance and testing should be considered from the start

Emergency and safety lighting is not a system that can simply be forgotten after installation. To ensure the system functions in an emergency, it must be regularly tested and the testing must be comprehensively documented. This applies to both the luminaires themselves and the power supply and switching.

The extent of the testing effort depends on the system's design. Self-contained battery luminaires involve different routines than centrally supplied systems. It also makes a difference whether tests are triggered manually or if automatic test functions and status indicators are present. Automatic tests can simplify procedures, but they do not replace the obligation to evaluate results and resolve faults.

Typical inspection points include the battery condition, charge level, visible fault messages, operating and status displays, and the simulation of a power failure. This checks whether the light or system switches over correctly and actually provides the safety function.

How often maintenance or testing is required cannot be answered with a blanket approach for every property. The specific intervals and operator obligations must always be aligned with the applicable regulations, the use of the building, and the system in use. Taking this into account during the selection process helps avoid unnecessary effort later on.

These questions will help you find the right solution

  • Does the luminaire need to be visible during normal operation or is it sufficient if it only turns on during a power failure?
  • What is the exact function of the luminaire? An exit sign luminaire, an escape route lighting, and a larger emergency lighting system do not automatically require the same type of circuit.
  • How is the system structured? The battery concept, switchover, test function, and future maintenance should be planned from the start using the Emergency lighting: Planning& Checklist .
  • Where would you like to go next practically? For more in-depth information, you will find suitable areas at MeinLEDcovering escape route lighting, LED emergency lighting and - depending on the system - the associated components such as emergency power batteries.